Automatic DB 5801 Manual de usuario Pagina 1

Busca en linea o descarga Manual de usuario para Herramientas Eléctricas Automatic DB 5801. Specification Bulletin 1045-31 Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 11
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
Conditions of Sale
STANDARD: Seller’s standard conditions of sale
set forth in Price Sheet 150 apply, except as modified
by the “SPECIAL WARRANTY PROVISIONS,” and
“WARRANTY QUALIFICATIONS” sections in this specifi-
cation bulletin.
SPECIAL TO THIS PRODUCT:
INCLUSIONS: S&C 6801 Automatic Switch Controls
combine sophisticated automatic control schemes with
RTU functionality, data logging, and advanced communi-
cation capabilities in a single package. Models are avail-
able for outdoor pole and pad mounting. 6801 Controls
manage distribution switches and can automatically sec-
tionalize a feeder based on factors such as overcurrent,
loss of voltage, and phase unbalance. One control can
automate one switch, and multiple controls can be pro-
grammed to communicate with each other using the
optional Intelli-Team
®
SG Automatic Restoration
System.
The IntelliTeam SG Automatic Restoration System
allows multiple switch controls to work together in teams,
using peer-to-peer communication, and quickly transfer
load to minimize the number of customers affected by a
fault or outage. The system uses distributed intelligence;
no central processing or SCADA is required (though fully
supported). Different types of switches, reclosers, and
controls can be included in the same team.
Utility personnel can communicate with 6801 Controls
to identify and isolate faults and restore service—with or
without a SCADA master station. DNP 3.0 is the supported
protocol, and two S&C approved radios can be installed
inside the enclosure, one for an automation network and
one as a SCADA getaway radio. An S&C SpeedNet™ Radio,
S&C IntelliCom
®
Mesh Radio, or a fiber-optic modem are
the recommended communication devices for use with
IntelliTeam SG.
6801 Controls provide true RMS voltage and
current readings. Over the operating temperature range
of -40° F to 158° F, current readings are accurate to ±0.5%
full scale, with a resolution of 1 ampere, RMS; voltage
readings are accurate to ±0.5% full scale, with a resolution
of 0.1 Vac. Phase angle readings are accurate to ±1° at
5% of full-scale current, with a resolution of °. The switch
controls have a current sensor input range of 0 to 800
amperes, RMS.
6801 Controls are configured specifically for fault detec-
tion. Over the overcurrent fault detection range of 0 to
4000 amperes, RMS, overcurrent readings are accurate
to ±0.5% full scale, with a resolution of 1 ampere, RMS.
6801 Controls have extensive data logging capabilities.
Voltage, current, and kVARs are logged every 15 minutes
for one month; daily maximum and minimum voltage, cur-
rent, kVARs, and power factor are logged for one year.
Overcurrent, loss-of-voltage, and fault magnitude and
duration data, as well as equipment diagnostics are also
recorded. A crystal-controlled, temperature-compensated
clock (GPS is optional) provides accurate time-stamping
of the data. The information collected at the switch loca-
tion is invaluable for analyzing problems on the circuit,
troubleshooting, optimizing performance of the installa-
tion, and planning for future requirements. With Intelli-
Team SG-equipped controls, data logging is especially
useful for determining the sequence of events during a
team reconfiguration, and for comparing the information
with substation data.
A PC operating under Windows® XP can be connected
via a DB9, or USB faceplate connector and IntelliLink®
Setup Software used to view real-time data, manage set
points, troubleshoot, and download historical data for
reports. Set points and data can also be accessed remotely
using S&C’s WinMon
®
Graphical User Interface, or Intelli-
Link
®
Remote Setup Software.
6801 Controls utilize a single power supply and
battery, eliminating the problems inherent in controls with
multiple power supplies and batteries. This highly efficient
power supply delivers 12 Vdc to the entire system, and
supplies 24-Vdc temperature-compensated battery charg-
ing and float charging to maximize battery life. Battery
condition is periodically checked under varying loads.
Detailed information on battery and power supply status
is available at the faceplate liquid-crystal display and is
accessible at remote locations in communication-device-
equipped controls. 6801 Controls for use with S&C switch-
ing devices can accept control power from a 100- to 140-Vac
or 200- to 280-Vac source, or S&C sensor outputs. If both ac
and sensor sources are available, the control automatically
uses control power and switches to sensor power if control
power is lost.
Automatic Sectionalizing
6801 Controls have automatic sectionalizing capabilities
that can improve circuit reliability when coordinated with
source-side reclosing devices. The controls can help
reduce loss of service and locate faulted line sections. Con-
trols equipped with IntelliTeam SG automatic circuit
reconfiguration can provide full restoration of unaffected
customer loads, if circuit capacity will allow it.
S&C 6801 Automatic Switch Controls
May 18, 2015
© S&C Electric Company 2011-2015, all rights reserved
Specification Bulletin 1045-31
Specications
Vista de pagina 0
1 2 3 4 5 6 ... 10 11

Indice de contenidos

Pagina 1 - Specications

Conditions of Sale STANDARD: Seller’s standard conditions of sale set forth in Price Sheet 150 apply, except as modified by the “SPECIAL WARRANTY P

Pagina 2 - How to Order

① Only available for 5801 Automatic Switch Controls with Suffix “-F01,” for use with Scada-Mate Switches or Scada-Mate CX Switches, or Suffix “-F02,”

Pagina 3

6801 Automatic Switch ControlDimensions in inchesS&C 6801 Automatic Switch ControlsS&C Specication Bulletin 1045-31 11

Pagina 4 - Optional Software

Shots to LockoutThe selectable shots-to-lockout feature prevents the source-side protective device from reclosing into a fault multiple times. Loss of

Pagina 5 - TABLE CONTINUED ▶

6801 Automatic Switch ControlsItem①Control SourceNumber of SwitchingDevices ControlledCatalog NumberBasic With GPS Module②6801 Automatic Switch Contro

Pagina 6 - Options—Continued

Mounting—Must Be SpecifiedMountingSuffix to Be Added to Switch Control Catalog NumberNo Enclosure-JB0▲Pole Mounting, in Padlockable Corrosion-Resista

Pagina 7

TABLE CONTINUED ▶① Total maximum continuous power is 12 watts. This is the available power for all communication equipment installed in the switch con

Pagina 8

① Total maximum continuous power is 12 watts. This is the available power for all communication equipment installed in the switch control. A maximum p

Pagina 9 - Accessories

① Use only with IntelliCom DA Mesh Radio Suffixes “-R201” and “-R203.”★ Radio power is restricted when using control power from three voltage senso

Pagina 10 - Voltage Phase Change Harness

TABLE CONTINUED ▶▲ Specify the appropriate catalog number suffix based on the frequency band range and application for the radio, from the following

Pagina 11 - 6801 Automatic Switch Control

① Use GPS Antenna, Surface Mount Catalog Number 007-001615-01 or Pole-Mounted Antenna Kit for GPS Catalog Number 903-002344-01.② Sixnet SLX-5ES-1 ha

Comentarios a estos manuales

Sin comentarios